(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.

Surge Protection Devices - Compact, Class II

Surge Protection Devices - Compact, Class II
  • Volume Discount

LT-C series compact surge protectors from Otowa Electric utilize built in disconnect mechanisms to protect against electrical surges and over-voltages. An integrated detaching mechanism helps to prevent smoke emission.

[Features]
・Integrated line-to-ground and ground-to-ground discharge protection.
・2-phase and 3-phase options available.
・Choose from 1.5kV, 1.8kV, or 2.0kV surge protection.
・2-phase and 3-phase options available.
・800V or 1000V of current discharge between line and ground possible.

PDF

Part Number

Configured Part Number is shown.

 
Part Number
LT-C12G801W
LT-C14G801W
LT-C32G801W
LT-C34G801W
LT-C35G102W
Part NumberMinimum order quantityVolume DiscountDays to Ship RoHSVoltage Maximum Continuous Operational Voltage Voltage protection level Direct current discharge starting voltage Voltage when starting operations Number of phases, number of wires
1 Piece(s)Available

8 Days or more

10200VAC275V1.5kVBetween line and ground 800V ± 20%Line 540V ± 10%Single-phase 2-line
1 Piece(s)Available

8 Days or more

-400VLine AC480V/ ground 280V1.8kVBetween line and ground 800V ± 20%Line 940V ± 10%Single-phase 2-line
1 Piece(s)Available

8 Days or more

10200VAC275V1.5kVBetween line and ground 800V ± 20%Line 540V ± 10%Three-phase three-line
1 Piece(s)Available

8 Days or more

-400VY wire connection AC 480 V/△ wire connection 280V1.8kVBetween line and ground 800V ± 20%Line 940V ± 10%Three-phase three-line
1 Piece(s)Available

8 Days or more

-500VY wire connection AC 550 V/△ wire connection 320 V2.0kVBetween line and ground 1000 V ± 20%Line 1100V ± 10%Three-phase three-line

Loading...

  1. 1

Basic Information

Application Power supply Model Integrated type Mounting method Cord direct removal
Class, category Class II Representative standards UL / CUL / TUV / CSA Dimension vertical(mm) 33.5
Dimension width(mm) 38 Dimension depth(mm) 28 Nominal Discharge Current (8/20 μs) 2500A
Maximum Discharge Current (8/20 μs) 5000A

Additional Products in this Category